Design of effluent treatment plant for Waste Tyre Pyrolysis Industry, Siltara, Raipur †

Author : Adireddi Hemanthnaidu a, (Mrs.) A. B. Soni *a and Amit Khare b

DOWNLOAD (604)

ABSTRACT


Appropriate design techniques, precise construction along with efficient operation as well as maintenance is primarily essential to the plants involving waste water treatment, to produce the residual amount of effluents which satisfies safe disposal standards which are recommended by the legal regulatory authorities. Main objective of this study was to design an efficient waste water treatment plant for Waste Tyre Pyrolysis Industry, Siltara. The design parameters as well as operational aspects involved in an Effluent Treatment Plant (ETP) especially for Waste Tyre Pyrolysis process were also studied. The parameters required in design stage have been looked into and the quantitative as well as qualitative aspects associated with effluent treatment were studied following empirical formula and standard IS codes. The pH reduced from 8.1 to 6.1; TSS: 3582-86 mg/L; TDS: 3558-118 mg/L; COD: 9819-137 mg/L and BOD: 4740-95 mg/L respectively. Finally treated water is being used in industry for other purposes, such as for ash quenching, spraying on coal etc.

KEYWORD


Effluent Treatment Plant (ETP), Waste Tyre Pyrolysis, design, Biological Oxygen Demand (BOD), Chemical Oxygen Demand (COD)